0086-13950598181

[email protected]

New Products

Latest News

Warning:
2018-10-22

Warning:

Warning: 1. Ensure personnel have been trained in the handling and proper use of batteries. Always wear the correct personal protection equipment (PPE) when handling batteries. 2. Battery maintenance checks should also be completed as part of your routine maintenance inspections. 3. Always wear the appropriate PPE when handling electrolyte. If splashed with electrolyte, immediately flush the affected area with clean water and seek medical advice. 4. Never add undiluted sulphuric acid to a battery. 5. Keep batteries upright to prevent electrolyte spillage. Electrolyte is a dilute sulphuric acid and is harmful to the skin. 6. Use tools with insulated handles when removing or fitting the battery. Never place tools or metal objects across the battery terminals. 7. During charging, the battery gives off explosive gases. Keep the battery in a well ventilated area and away from naked flames and sparks. Smoking is also prohibited. 8. Generator set batteries, by law, must not be disposed of with household waste. Batteries contain hazardous materials and in the charged state, each cell contains electrodes of lead metal (Pb) and lead (IV) dioxide (PbO2) in an electrolyte of about 33.5% w/w (6 Molar) sulphuric acid (H2SO4). In the discharged state both electrodes turn into lead (II) sulphate (PbSO4) and the electrolyte loses its dissolved sulphuric acid and becomes primarily water.It can be damaging to the environment to send these to landfill, burning batteries can also cause atmospheric pollution.Dealing with lead acid batteries can be hazardous so it is important to follow all safety guidelines. Batteries are an essential part of the generator set and should be maintained appropriately. Keep the battery area clean and dry and ensure any vent caps are tight (if fitted). Clean the battery case with one of the following cleaning solutions: • A mixture of 0.1 kg (0.2 lb) of baking soda and 1 L (1 qt) of clean water • A mixture of 0.1 L (0.11 qt) of ammonia and 1 L (1 qt) of clean water Thoroughly rinse the battery case with clean water. All battery connections must be kept clean and tight. Use a fine grade of sandpaper to clean the terminals and the cable clamps.Clean the items until the surfaces are bright or shiny. Do not remove material excessively. Excessive removal of material can terminal protector to prevent corrosion. The electrolyte level should be covering the plates/grids (1/2 inch / 13 mm) within the battery to maximize full charge transfer. If the liquid level is below the plates/grids, only add distilled water; never add battery acid to top up the volume, as the addition of extra acid will destroy the grids. It is recommended to check the electrolyte and condition of the batteries every 500 running hours. In high ambient conditions, it is recommended to use thermal compensation and check electrolyte levels more frequently, for example every 200 running hours. These checks should also be completed as p...

Genset Battery Removal and Fitting

2018-10-31 15:13:18
Battery acid can burn clothing and skin or cause blindness if it leaks. Please wear protective clothing when inspecting a
battery prior to its disconnection / transportation.
• Ensure the battery to be fitted is filled with the correct levels and mixture of electrolyte and is fully charged.
• If vents are fitted, ensure they are firmly in place.
• Before removing a battery, carry out a thorough inspection of its condition. Use a torch if visibility is poor to check all sides
of the battery for any marks, dents or leaks.
• If the battery has any severe dents or leaks please contact your local Dealer for assistance. DO NOT attempt to remove the
battery.
• Disconnect the battery safely before inspecting it (see below).
• Disconnect any battery charging circuitry before fitting the battery.
• When removing a battery for whatever reason always ensure all load is removed before disconnecting the battery so that
no sparks are created. Disconnect the negative cable first by the positive cable to avoid short circuit against any
metal framework, then remove the hold down clamp or strap securing the battery base. The battery can be heavy so
please be careful when lifting and carrying the battery. Seek assistance if required.
• When refitting the battery, ensure the terminal posts are correctly aligned with the cables to avoid wrong connection
and place the new battery into the hold-down tray and reattach the hold-down clamp or strap. Attach and tighten the
positive battery cable to the positive terminal first. Then attach and tighten the negative battery cable to the negative
terminal.
• Keep the battery terminals clean and free from corrosion and lightly smear the connections with petroleum jelly.
• Ensure battery terminals are tight as loose battery terminals can reduce battery life and are a fire hazard.
• Ensure the positive terminal on each battery is covered correctly.
• When fitting a battery and / or battery charger please ensure they are appropriately matched. Please consult a qualified
technician if unsure.
• During transport, please ensure that battery terminals are covered to remove the possibility of a short circuit.
• Keep the battery upright at all times.
 
Got Free Inquiry Now Please click here for inquiry
If you have questions or suggestions,please leave us a message,we will reply you as soon as we can!